SR EN 60567:2006
Echipamente electrice imersate în ulei. Eşantioane de gaz şi de ulei pentru analiza gazelor libere şi dizolvate. Ghid
Deals with the techniques for sampling free gases from gas-collecting relays and for sampling oil from oil-filled equipment such as power and instrument transformers, reactors, bushings, oil-filled cables and oil-filled tank-type capacitors. Three methods of sampling free gases and three methods of sampling oil are described; the choice between the methods often depends on the apparatus available and on the quantity of oil needed for analysis. Before analysing the gases dissolved in oil, they must first be extracted from the oil. Three basic methods are described, one using extraction by vacuum (Toepler and partial degassing), another by displacement of the dissolved gases by bubbling the carrier gas through the oil sample (stripping), and the last one by partition of gases between the oil sample and a small volume of the carrier gas (head space). The gases are analysed quantitatively after extraction by gas chromatography; a method of analysis is described. Free gases from gas-collecting relays are analysed without preliminary treatment. The preferred method for assuring the
Status :
Anulat
Data aprobării : 22.02.2006
Data publicării : 24.02.2006
Data anulării : 24.11.2014
Număr de pagini : 133
ICS : 17.220.99 Alte standarde referitoare la electricitate si magnetism,29.035.99 Alte materiale electroizolante,29.040.10 Uleiuri electroizolante
Comitet tehnic : 5 - Materiale și fluide electroizolante
- Inlocuieste SR EN 60567:1999
- Inlocuit prin SR EN 60567:2012
EN